Guide
How many square feet does a ton of AC cool
A ton cools far more house in Minneapolis than in Miami, so no single rule of thumb can be right.
Short answer
About 520 square feet per ton in a mixed climate such as Washington DC or St Louis, for an average house with 8 ft ceilings, falling to about 380 in south Florida and rising to about 620 in Minnesota. So a 3 ton unit cools roughly 1,130 to 1,850 sq ft depending on climate, and a 2,000 sq ft house in a mixed climate needs about 4 tons. A Manual J calculation for the actual house is the figure to buy on.
Square feet per ton by climate zone
One ton of air conditioning is 12,000 BTU per hour of cooling. How much floor that covers depends on how many BTU per square foot of heat the house gains, which is set mostly by climate and then by how well the house keeps heat out.
| Zone | Examples | Well sealed | Average house | Leaky, older |
|---|---|---|---|---|
| Zone 1, hot humid | Miami, Key West, Honolulu | 400 | 380 | 340 |
| Zone 2, hot | Houston, Orlando, Phoenix, New Orleans | 440 | 430 | 400 |
| Zone 3, warm | Atlanta, Dallas, Los Angeles, Charlotte | 500 | 480 | 440 |
| Zone 4, mixed | Washington DC, Seattle, St Louis, Nashville | 550 | 520 | 480 |
| Zone 5, cool | Chicago, Denver, Boston, Detroit | 600 | 570 | 520 |
| Zone 6, cold | Minneapolis, Burlington, Helena | 670 | 620 | 550 |
| Zone 7, very cold | Duluth, Grand Forks, International Falls | 750 | 690 | 600 |
| Zone 8, subarctic | Fairbanks, Barrow | 800 | 740 | 670 |
Not sure of your zone? Look up where your county falls.
What each AC size covers
| Unit | Zone 1 | Zone 2 | Zone 3 | Zone 4 | Zone 5 | Zone 6 |
|---|---|---|---|---|---|---|
| 1.5 ton (18,000 BTU) | 560 | 640 | 720 | 780 | 850 | 920 |
| 2 ton (24,000 BTU) | 750 | 850 | 960 | 1,040 | 1,140 | 1,230 |
| 2.5 ton (30,000 BTU) | 940 | 1,070 | 1,190 | 1,300 | 1,420 | 1,540 |
| 3 ton (36,000 BTU) | 1,130 | 1,280 | 1,430 | 1,560 | 1,700 | 1,850 |
| 3.5 ton (42,000 BTU) | 1,320 | 1,490 | 1,670 | 1,820 | 1,990 | 2,150 |
| 4 ton (48,000 BTU) | 1,510 | 1,710 | 1,910 | 2,080 | 2,270 | 2,460 |
| 5 ton (60,000 BTU) | 1,880 | 2,130 | 2,390 | 2,590 | 2,840 | 3,080 |
What size AC for 1,500, 2,000 or 3,000 sq ft
Going the other way, from the house to the unit, the air conditioner size calculator rounds the load up to the next size central systems are sold in. The calculator stays within 15 percent of the load where it can, because an oversized unit cools the air before it has dried it.
| House | Zone 2 | Zone 4 | Zone 6 |
|---|---|---|---|
| 1,000 sq ft | 2.3 t: 2.5 ton | 1.9 t: 2 ton | 1.6 t: 2 ton, over 15% |
| 1,200 sq ft | 2.8 t: 3 ton | 2.3 t: 2.5 ton | 2 t: 2 ton |
| 1,500 sq ft | 3.5 t: 4 ton | 2.9 t: 3 ton | 2.4 t: 2.5 ton |
| 1,800 sq ft | 4.2 t: 4.5 ton | 3.5 t: 3.5 ton | 2.9 t: 3 ton |
| 2,000 sq ft | 4.7 t: 5 ton | 3.9 t: 4 ton | 3.3 t: 3.5 ton |
| 2,500 sq ft | 5.9 t: two systems | 4.8 t: 5 ton | 4.1 t: 4.5 ton |
| 3,000 sq ft | 7 t: two systems | 5.8 t: two systems | 4.9 t: 5 ton |
Residential central air conditioners top out at 5 tons, so a house whose load is above that is split into two systems, often one per floor. The sizing chart lists loads for every common house size in all eight zones.
Why "square feet per ton" misleads
The figure is an average, and every one of the things it averages over moves it a long way:
- Climate. A ton covers about 380 sq ft in zone 1 and 620 in zone 6, so any single number is wrong for most of the country.
- The house. In zone 4, a well-sealed house gets 550 sq ft per ton and a leaky one 480.
- Ceiling height. The load follows the volume of air, not the floor. With 10 ft ceilings the zone 4 figure drops from 520 to 420.
- Sun. Big west or south windows take it down to 450; heavy shade raises it to 580.
- Rounding. Units come in half-ton steps. A 1,300 sq ft house in zone 4 has a load of 30,063 BTU, just over 2.5 tons, and the next size up is 20 percent over the load. That is the case where a Manual J pays for itself, by showing whether the smaller unit is enough.
Sizing by square feet and rounding up at every step is how houses end up with oversized units, and an oversized unit is the more expensive mistake: it short cycles, leaves the house clammy and wears the compressor. Why an oversized system is worse, not safer explains the mechanism, and what a Manual J measures explains how to ask for one. Use the tables here to check a quote, not to replace one.
Reading the size of the unit you have
The tonnage is usually coded in the outdoor unit's model number as thousands of BTU: a two-digit number such as 24, 30, 36, 42, 48 or 60 means 2, 2.5, 3, 3.5, 4 or 5 tons. If the house cools quickly but feels humid, that is a sign the unit may be oversized; if it ran all afternoon on the hottest days and still held temperature, that is what a correctly sized unit does.